Unidrive M100 User Guide 115
Issue Number: 1
Table 11-13 AC Input current and fuse ratings (400 V)
Ensure cables used suit local wiring regulations.
Table 11-14 Cable ratings (100 V)
Table 11-15 Cable ratings (200 V)
Model
Typical input current
Maximum continuous
input current
Maximum overload
input current
Fuse rating
IEC gG Class CC or Class J
Maximum Maximum
AA A A A
02400013
2.1
2.4
6
502400018
2.6
2.9
02400023
3.1
3.5
02400032
4.7
5.1
10
02400041
5.8
6.2 10
03400056
8.3
8.7 10 10
03400073
10.2
12.2
16
16
03400094
13.1
14.8 20
04400135
14.0
16.3 20 20
04400170
18.5
20.7 25 25
The nominal cable sizes below are only a guide. The mounting and grouping of cables affects their current-carrying capacity, in some cases
smaller cables may be acceptable but in other cases a larger cable is required to avoid excessive temperature or voltage drop. Refer to
local wiring regulations for the correct size of cables.
CAUTION
Model
Cable size (IEC 60364-5-52)
mm
2
Cable size (UL508C)
AWG
Input Output Input Output
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
01100017
11
16 16
01100024
1.5 1
14 16
02100042
2.5 1
12 16
02100056
41
10 16
Model
Cable size (IEC 60364-5-52)
mm
2
Cable size (UL 508C)
AWG
Input Output Input Output
Nominal Maximum Nominal Maximum Nominal Maximum Nominal Maximum
01200017
11
16 16
01200024
11
16 16
01200033
11
16 16
01200042
11
16 16
02200024
11
16 16
02200033
11
16 16
02200042
11
16 16
02200056
2.5/1.5 1
12/14 16
02200075
2.5
11216
03200100
4
1.5 10/12 14
04200133
4/2.5 2.5
10 12
04200176
42.5
10 12