User guide
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running
the motor
Optimization NV Media Card
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
102 Unidrive M100 User Guide
Issue Number: 1
10.9 Menu 10: Status and trips
Parameter
Range
(Ú) Default (Ö)
Type
OL OL
10.001 DriveOK Off(0)orOn(1) RO Bit ND NC PT
10.002 Drive Active Off (0) or On (1)
RO Bit ND NC PT
10.003 Zero Frequency Off (0) or On (1)
RO Bit ND NC PT
10.004
Running At or Below Minimum
Frequency
Off (0) or On (1)
RO Bit ND NC PT
10.005 Below Set Frequency Off (0) or On (1)
RO Bit ND NC PT
10.006 At Frequency Off (0) or On (1)
RO Bit ND NC PT
10.007 Above Set Frequency Off (0) or On (1)
RO Bit ND NC PT
10.008 Rated Load Reached Off (0) or On (1)
RO Bit ND NC PT
10.009 Current Limit Active Off (0) or On (1)
RO Bit ND NC PT
10.010 Regenerating Off (0) or On (1)
RO Bit ND NC PT
10.011 BrakingIGBTActive Off(0)orOn(1)
RO Bit ND NC PT
10.012 Braking Resistor Alarm Off (0) or On (1)
RO Bit ND NC PT
10.013 Reverse Direction Commanded Off (0) or On (1)
RO Bit ND NC PT
10.014 Reverse Direction Running Off (0) or On (1)
RO Bit ND NC PT
10.015 Supply Loss Off (0) or On (1)
RO Bit ND NC PT
10.016 Under Voltage Active Off (0) or On (1)
RO Bit ND NC PT
10.017 Motor Overload Alarm Off (0) or On (1)
RO Bit ND NC PT
10.018 Drive Over-temperature Alarm Off (0) or On (1)
RO Bit ND NC PT
10.019 Drive Warning Off (0) or On (1)
RO Bit ND NC PT
10.020 Trip 0 0 to 255
RO Txt ND NC PT PS
10.021 Trip 1 0 to 255
RO Txt ND NC PT PS
10.022 Trip 2 0 to 255
RO Txt ND NC PT PS
10.023 Trip 3 0 to 255
RO Txt ND NC PT PS
10.024 Trip 4 0 to 255
RO Txt ND NC PT PS
10.025 Trip 5 0 to 255
RO Txt ND NC PT PS
10.026 Trip 6 0 to 255
RO Txt ND NC PT PS
10.027 Trip 7 0 to 255
RO Txt ND NC PT PS
10.028 Trip 8 0 to 255
RO Txt ND NC PT PS
10.029 Trip 9 0 to 255
RO Txt ND NC PT PS
10.030 Braking Resistor Rated Power 0.0 to 99999.9 kW 0.0 kW RW Num US
10.031
Braking Resistor Thermal Time
Constant
0.00 to 1500.00 s 0.00 s RW Num US
10.032 External Trip Off (0) or On (1) Off (0) RW Bit NC
10.033 Drive Reset Off (0) or On (1) Off (0) RW Bit NC
10.034 Number Of Auto-reset Attempts
NonE (0), 1 (1), 2 (2),
3(3), 4(4), 5(5),inF
NonE (0) RW Txt US
10.035 Auto-reset Delay 0.0 to 600.0 s 1.0 s RW Num US
10.036 Auto-reset Hold Drive Healthy Off (0) or On (1) Off (0) RW Bit US
10.037 Action On Trip Detection 0 to 31 0 RW Num US
10.038 UserTrip 0to255
RW Num ND NC
10.039
Braking Resistor Thermal
Accumulator
0.0 to 100.0 %
RO Num ND NC PT
10.040 Status Word 0 to 32767
RO Num ND NC PT
10.041 Trip 0 Date 00-00-00 to 31-12-99
RO Date ND NC PT PS
10.042 Trip 0 Time 00:00:00 to 23:59:59
RO Time ND NC PT PS
10.043 Trip 1 Date 00-00-00 to 31-12-99
RO Date ND NC PT PS
10.044 Trip 1 Time 00:00:00 to 23:59:59
RO Time ND NC PT PS
10.045 Trip 2 Date 00-00-00 to 31-12-99
RO Date ND NC PT PS
10.046 Trip 2 Time 00:00:00 to 23:59:59
RO Time ND NC PT PS
10.047 Trip 3 Date 00-00-00 to 31-12-99
RO Date ND NC PT PS
10.048 Trip 3 Time 00:00:00 to 23:59:59
RO Time ND NC PT PS
10.049 Trip 4 Date 00-00-00 to 31-12-99
RO Date ND NC PT PS
10.050 Trip 4 Time 00:00:00 to 23:59:59
RO Time ND NC PT PS
10.051 Trip 5 Date 00-00-00 to 31-12-99
RO Date ND NC PT PS