5.9 Displaying parameters with non-default values only
By entering 12000 in Pr xx.00, the only parameters that will be visible to the user will be
those containing a non-default value. This function does not require a drive reset to
become active. In order to deactivate this function, return to Pr xx.00 and enter a value
of 0.
Please note that this function can be affected by the access level enabled, refer to
section 5.11 Parameter access level and security for further information regarding
access level.
5.10 Displaying destination parameters only
By entering 12001 in Pr xx.00, the only parameters that will be visible to the user will be
destination parameters. This function does not require a drive reset to become active. In
order to deactivate this function, return to Pr xx.00 and enter a value of 0.
Please note that this function can be affected by the access level enabled, refer to
section 5.11 Parameter access level and security for further information regarding
access level.
5.11 Parameter access level and security
The parameter access level determines whether the user has access to menu 0 only or
to all the advanced menus (menus 1 to 22) in addition to menu 0.
The user security determines whether the access to the user is read only or read write.
Both the user security and parameter access level can operate independently of each
other as shown in the table below:
RW = Read / write access RO = Read only access
The default settings of the drive are parameter access level L1 and user security open,
i.e. read / write access to menu 0 with the advanced menus not visible.
Parameter
access level
User security Menu 0 status
Advanced
menus status
L1 Open RW Not visible
L1 Closed RO Not visible
L2 Open RW RW
L2 Closed RO RO