User guide

Unidrive SP Short Form Guide 45
Issue Number: 2 www.controltechniques.com
Safety
Information
Product
Information
Mechanical
Installation
Electrical
Installation
Getting Started
Basic parameters
Running the
motor
SMARTCARD
Advanced
parameters
Diagnostics
UL Listing
Information
SM-Keypad Plus set-up menus
Table 5-1 Menu 40 parameter descriptions
Table 5-2 Menu 41 parameter descriptions
5.6 Changing the operating mode
Changing the operating mode returns all parameters to their default value, including the
motor parameters. (Pr 0.49 Security status and Pr 0.34 User security code are not
affected by this procedure.)
Procedure
Use the following procedure only if a different operating mode is required:
1. Ensure the drive is not enabled, i.e. terminal 31 is open or Pr 6.15 is OFF (0)
2. Enter either of the following values in Pr 0.00, as appropriate:
1253 (Europe, 50Hz AC supply frequency)
1254 (USA, 60Hz AC supply frequency)
Parameter
Range(
Ú)
40.00 Parameter 0 0 to 32767
40.01 Language selection
English (0), Custom (1), French (2),
German (3), Spanish (4), Italian (5)
40.02 Software version
999999
40.03 Save to flash
Idle (0), Save (1), Restore (2),
Default (3)
40.04 LCD contrast
0 to 31
40.05
Drive and attribute database upload was
bypassed
Updated (0), Bypass (1)
40.06 Browsing favourites control
Normal (0), Filter (1)
40.07 Keypad security code
0 to 999
40.08 Communication channel selection
Disable (0), Slot1 (1), Slot2 (2),
Slot3 (3), Slave (4), Direct (5)
40.09 Hardware key code
0 to 999
40.10 Drive node ID (Address)
0 to 255
40.11 Flash ROM memory size
4Mbit (0), 8Mbit (1)
40.19 String database version number
0 to 999999
40.20 Screen saver strings and enable
None (0), Default (1), User (2)
40.21 Screen saver interval
0 to 600
40.22 Turbo browse time interval
0 to 200ms
Parameter
Range(
Ú)
41.00 Parameter 0 0 to 32767
41.01 to
41.50
Browsing filter source F01 to F50 Pr 0.00 to Pr 391.51
41.51 Browsing favourites control Normal (0), Filter (1)