User guide
120 Unidrive SP Short Form Guide
www.controltechniques.com Issue Number: 2
Field wiring
Size 0 to 4
• Class 1 60/75°C (140/167°F) copper wire only is used in the installation
Size 5 and 6
• Class 1 75°C (167°F) copper wire only is used in the installation
Field wiring connectors
Sizes 4 to 6
• UL listed wire connectors are used for terminating power circuit field wiring, e.g.
Ilsco TA series
AC supply specification
The drive is suitable for use in a circuit capable of delivering not more than 100,000rms
symmetrical Amperes at 264Vac rms maximum (200V drives), 528Vac rms maximum
(400V drives) or 600Vac rms maximum (575V and 690V drives).
Maximum continuous output current
The drive models are listed as having the maximum continuous output currents (FLC)
shown in Table 11-1, Table 11-2, Table 11-3 and Table 11-4.
Table 11-1 Maximum continuous output current (200V drives)
Table 11-2 Maximum continuous output current (400V drives)
Model FLC (A) Model FLC (A)
0201 2.2 2201 15.5
0202 3.1 2202 22
0203 4.0 2203 28
0204 5.7 3201 42
0205 7.5 3202 54
1201 5.2 4201 68
1202 6.8 4202 80
1203 9.6 4203 104
1204 11 5201 130
5202 154
Model FLC (A) Model FLC (A)
0401 1.3 2401 15.3
0402 1.7 2402 21
0403 2.1 2403 29
0404 3.0 2404 29
0405 4.2 3401 35
1401 2.8 3402 43
1402 3.8 3403 56
1403 5.0 4401 68
1404 6.9 4402 83
1405 8.8 4403 104
1406 11 5401 138
5402 168
6401 205
6402 236