Generally the drive rated current is higher than the matching motor rated current
allowing a higher level of overload than the default setting as illustrated by the example
of a typical 4 pole motor.
The time allowed in the overload region is proportionally reduced at very low output
frequency on some drive ratings.
2.2 Nameplate description
See Figure 3-8 for location of rating labels.
Figure 2-1 Typical drive rating labels for size 0
Operating mode CL from cold CL from 100% OL from cold OL from 100%
Normal Duty overload with motor rated current
= drive rated current
110% for 165s 110% for 9s
110% for 165s
110% for 9s
Heavy Duty overload with motor rated current =
drive rated current
150% for 60s 150% for 8s 129% for 97s 129% for 15s
The maximum overload level which can be attained is independent of the speed.
NOTE
Model
SP0204 1.1kW
S/N: 3000005001
SPZ 2 M/TL
Serial
number
Rating
Please read the manual before connecting
Electric Shock Risk: Wait 10 mins
between disconnecting supply
and accessing terminals
E171230
Date code
Approvals
Approvals label
I/P 200-240V 50-60Hz 1/3ph 13.5/7.9A