User manual
IEC61131 User and Reference Manual
April 22, 2008
572
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
23
2
16-Bit Frozen Counter Event without Time
23
3
32-Bit Frozen Delta Counter Event without Time
23
4
16-Bit Frozen Delta Counter Event without Time
23
5
32-Bit Frozen Counter Event with Time
23
6
16-Bit Frozen Counter Event with Time
23
7
32-Bit Frozen Delta Counter Event with Time
23
8
16-Bit Frozen Delta Counter Event with Time
30
0
Analog Input - All Variations
1
06
30
1
32-Bit Analog Input
129, 130
00, 01
30
2
16-Bit Analog Input
129, 130
00, 01
30
3
32-Bit Analog Input without Flag
129, 130
00, 01
30
4
16-Bit Analog Input without Flag
129, 130
00, 01
30
5
Short Floating Point Analog Input
129, 130
00, 01
31
0
Frozen Analog Input - All Variations
31
1
32-Bit Frozen Analog Input
31
2
16-Bit Frozen Analog Input
31
3
32-Bit Frozen Analog Input with Time of Freeze
31
4
16-Bit Frozen Analog Input with Time of Freeze
31
5
32-Bit Frozen Analog Input without Flag
31
6
16-Bit Frozen Analog Input without Flag
32
0
Analog Change Event - All Variations
1
06,07,08
32
1
32-Bit Analog Change Event without Time
129,130
17,28
32
2
16-Bit Analog Change Event without Time
129,130
17,28
32
3
32-Bit Analog Change Event with Time
129,130
17,28
32
4
16-Bit Analog Change Event with Time
129,130
17,28