DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
21
0
Frozen Counter - All Variations
1
06
21
1
32-Bit Frozen Counter
129, 130
00, 01
21
2
16-Bit Frozen Counter
129, 130
00, 01
21
3
32-Bit Frozen Delta Counter
21
4
16-Bit Frozen Delta Counter
21
5
32-Bit Frozen Counter with Time of Freeze
21
6
16-Bit Frozen Counter with Time of Freeze
21
7
32-Bit Frozen Delta Counter with Time of
Freeze
21
8
16-Bit Frozen Delta Counter with Time of
Freeze
21
9
32-Bit Frozen Counter without Flag
129, 130
00, 01
21
10
16-Bit Frozen Counter without Flag
129, 130
00, 01
21
11
32-Bit Frozen Delta Counter without Flag
21
12
16-Bit Frozen Delta Counter without Flag
22
0
Counter Change Event - All Variations
1
06,07,08
22
1
32-Bit Counter Change Event without Time
129, 130
17, 28
22
2
16-Bit Counter Change Event without Time
129, 130
17, 28
22
3
32-Bit Delta Counter Change Event without
Time
22
4
16-Bit Delta Counter Change Event without
Time
22
5
32-Bit Counter Change Event with Time
22
6
16-Bit Counter Change Event with Time
22
7
32-Bit Delta Counter Change Event with Time
22
8
16-Bit Delta Counter Change Event with Time
23
0
Frozen Counter Event - All Variations
23
1
32-Bit Frozen Counter Event without Time