User manual

IEC61131 User and Reference Manual
April 22, 2008
564
DNP V3.00
DEVICE PROFILE DOCUMENT
IMPLEMENTATION OBJECT
This table describes the objects, function codes and qualifiers used in the device:
OBJECT
REQUEST
(slave must parse)
RESPONSE
(master must parse)
Obj
Var
Description
Func
Codes
(dec)
Qual
Codes
(hex)
Func
Codes
Qual
Codes
(hex)
32
5
Short Floating Point Analog Change Event
without Time
129,130
17,28
33
0
Frozen Analog Event - All Variations
33
1
32-Bit Frozen Analog Event without Time
33
2
16-Bit Frozen Analog Event without Time
33
3
32-Bit Frozen Analog Event with Time
33
4
16-Bit Frozen Analog Event with Time
40
0
Analog Output Status - All Variations
1
06
40
1
32-Bit Analog Output Status
129, 130
00, 01
40
2
16-Bit Analog Output Status
129, 130
00, 01
40
3
Short Floating Point Analog Output Status
129, 130
00, 01
41
0
Analog Output Block - All Variations
41
1
32-Bit Analog Output Block
3, 4, 5,
6
17, 28
129
echo of
request
41
2
16-Bit Analog Output Block
3, 4, 5,
6
17, 28
129
echo of
request
41
3
Short Floating Point Analog Output Block
3, 4, 5,
6
17, 28
129
echo of
request
50
0
Time and Date - All Variations
50
1
Time and Date
2 (see
4.14)
07 where
quantity = 1
50
2
Time and Date with Interval
51
0
Time and Date CTO - All Variations
51
1
Time and Date CTO
129, 130
07,
quantity=1
51
2
Unsynchronized Time and Date CTO
129, 130
07,
quantity=1
52
0
Time Delay - All Variations
52
1
Time Delay Coarse
129
07,
quantity=1