User manual
IEC61131 User and Reference Manual
April 22, 2008
557
Device Name: SCADAPack controllers
Highest DNP Level Supported:
For Requests 2
For Responses 2
Device Function:
Master Slave
Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels
Supported (the complete list is described in the attached table):
Function code 14 (warm restart)
Function code 20 (Enable Unsolicited Messages) for class 1, 2, 3 objects only.
Function code 21 (Disable Unsolicited Messages) for class 1, 2, 3 objects only.
Object 41, variation 1 (32-bit analog output block)
Maximum Data Link Frame Size (octets):
Transmitted 292
Received (must be 292)
Maximum Application Fragment Size (octets):
Transmitted 2048
Received 2048
Maximum Data Link Re-tries:
None
Fixed at
Configurable, range 0 to 255
Maximum Application Layer Re-tries:
None
Configurable, range 0 to 255
Requires Data Link Layer Confirmation:
Never