The Number of Points displays the number of Short Floating Point Analog Outputs reported by the
RTU. This value will increment with the addition of each configured Short Floating Point Analog
Input point. The maximum number of points is 9999. The maximum number of actual points will
depend on the memory available in the controller.
The Starting Address parameter specifies the DNP address of the first Short Floating Point Analog
Output point.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
TelePACE / ISaGRAF (MSW First) Most Significant Word in first register.
Reverse (LSW First) Least Significant Word in first register.
The Allow Duplicate Modbus Addresses checkbox determines if the Modbus I/O database
addresses assigned to the DNP data points must be unique. Check this box if you want to allow more
than one point to use the same Modbus address.