535
maximum number of points is 9999. The maximum number of actual points will depend on the
memory available in the controller.
The Starting Address parameter specifies the DNP address of the first 16-bit Analog Output point.
The Word Order selection specifies the word order of the 32-bit value. The selections are:
TelePACE Least Significant Word in first register.
ISaGRAF Most Significant Word in first register.
The Allow Duplicate Modbus Addresses checkbox determines if the Modbus I/O database
addresses assigned to the DNP data points must be unique. Check this box if you want to allow more
than one point to use the same Modbus address.