User manual
IEC61131 User and Reference Manual
April 22, 2008
531
30001 through 39998
40001 through 49998
The Class of Event Object parameter specifies the event object class the Short
Floating Point Analog Input is assigned. If Unsolicited reporting is not required for a
DNP point, it is recommended to set its Class 0 or None. The selections are:
None
Class 1
Class 2
Class 3
The Deadband parameter specifies whether the RTU generates events. The value entered is the
minimum number of counts that the Short Floating Point Analog Input must change since it was last
reported. Setting this value to zero disables generating events for the Short Floating Point Analog
Inputs.
The Allow Duplicate Modbus Addresses checkbox determines if the Modbus I/O database
addresses assigned to the DNP data points must be unique. Check this box if you want to allow more
than one point to use the same Modbus address.
Click the OK button to accept the Short Floating Point Analog Input parameters and close the DNP
Settings dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current Short Floating Point Analog Input to the DNP configuration.
Click the Copy button to copy the current Short Floating Point Analog Input parameters to the next
DNP Address.
Click the Delete button to delete the current Short Floating Point Analog Input.
Click the Move Up button to move the current Short Floating Point Analog Input up one position in
the tree control branch.
Click the Move Down button to move the current Short Floating Point Analog Input down one
position in the tree control branch.
16-Bit Analog Outputs Configuration
The 16-Bit Analog Outputs property page is selected for editing by clicking 16-Bit Analog Outputs
in the tree control section of the DNP Settings window. When selected the 16-Bit Analog Outputs
property page is active.