526
Adding 32-Bit Analog Inputs
32-Bit Analog Inputs are added to the DNP configuration using the 16-Bit Analog Input property
page. To add a 32-Bit Analog Input:
Select 32-Bit Analog Inputs in the tree control section of the DNP Settings window.
Click the Add button in the 32-Bit Analog Inputs property page.
The 32-Bit Analog Input property page is now displayed.
Edit the 32-Bit Analog Input parameters as required and then click the Add button.
As 32-Bit Analog Inputs are defined they are added as leaves to the 32-Bit Analog Inputs branch of
the tree control. When 32-Bit Analog Inputs are defined the 32-Bit Analog Inputs branch will display
a collapse / expand control to the left of the branch. Click this control to display all defined 32-Bit
Analog Inputs.
The 32-Bit Analog Input parameters are described in the following paragraphs.
The DNP Address window displays the DNP 32-Bit Analog Input address of the point. Each 32-Bit
Analog Input is assigned a DNP address as they are defined. The DNP point address starts at the
value set in the 32-bit Analog Input configuration dialog and increments by one with each defined
32-Bit Analog Input.
The Modbus Address parameter specifies the Modbus addresses of the 32-Bit Analog Input
assigned to the DNP Address. 32-Bit Analog Inputs use two consecutive Modbus registers for each
assigned DNP Address, the address that is entered in this box and the next consecutive Modbus
register. The SCADAPack and Micro16 controllers use Modbus addressing for all analog inputs.
Refer to the I/O Database Registers section of the TelePACE Ladder Logic Reference and User
Manual for complete information on analog input addressing in the SCADAPack and Micro16
controllers. Valid Modbus addresses are:
30001 through 39998