User manual

IEC61131 User and Reference Manual
April 22, 2008
523
40001 through 49999
The Class of Event Object parameter specifies the event object class assigned to the 16-Bit Analog
Input is assigned. If Unsolicited reporting is not required for a point, it is recommended to set its
Class to None. All data points automatically become members of Class 0 or None (static data). The
selections are:
None
Class 1
Class 2
Class 3
The Deadband parameter specifies the minimum number of counts that the 16-Bit Analog Input
must change since it was last reported in order to generate an event. Valid deadband values are 0 to
65535. A deadband of zero will cause any change to create an event.
The Allow Duplicate Modbus Addresses checkbox determines if the Modbus I/O database
addresses assigned to the DNP data points must be unique. Check this box if you want to allow more
than one point to use the same Modbus address.
Click the OK button to accept the 16-Bit Analog Input parameters and close the DNP Settings
dialog.
Click the Cancel button to close the dialog without saving any changes.
Click the Add button to add the current 16-Bit Analog Input to the DNP configuration.
Click the Copy button to copy the current 16-Bit Analog Input parameters to the next DNP Address.
Click the Delete button to delete the current 16-Bit Analog Input.
Click the Move Up button to move the current 16-Bit Analog Input up one position in the tree
control branch.
Click the Move Down button to move the current 16-Bit Analog Input down one position in the tree
control branch.
32-Bit Analog Inputs Configuration
The 32-Bit Analog Inputs property page is selected for editing by clicking 32-Bit Analog Inputs in
the tree control section of the DNP Settings window. When selected the 32-Bit Analog Inputs
property page is active.