User manual
IEC61131 User and Reference Manual
April 22, 2008
518
Adding Binary Outputs
Binary Outputs are added to the DNP configuration using the Binary Output property page. To add a
Binary Output:
Select Binary Outputs in the tree control section of the DNP Settings window.
Click the Add button in the Binary Outputs property page.
The Binary Output property page is now displayed.
Edit the Binary Output parameters as required and then click the Add button.
As Binary Outputs are defined they are added as leaves to the Binary Outputs branch of the tree
control. When Binary Outputs are defined the Binary Outputs branch will display a collapse / expand
control to the left of the branch. Click this control to display all defined Binary Outputs.
The Binary Output parameters are described in the following paragraphs.
The DNP Address window displays the DNP Binary Output address of the point. Each Binary
Output is assigned a DNP address as they are defined. The DNP point address starts at the value
defined in the Binary Outputs dialog and increments by one with each defined Output.
The Modbus Address 1 parameter specifies the Modbus address of the Binary Output assigned to
the DNP Address. The SCADAPack and Micro16 controllers use Modbus addressing for all digital
outputs. Refer to the I/O Database Registers section of the TelePACE Ladder Logic Reference
Manual for complete information on digital output addressing in the SCADAPack and Micro16
controllers. Valid Modbus addresses are:
00001 through 09999
The Modbus Address 2 parameter specifies the second Modbus address of the second Binary
Output assigned to the DNP Address when the Paired control type is selected. This selection is not
active when the control type is Not Paired. Valid Modbus addresses are: