Binary Outputs parameters are viewed in this property page.
The Number of Points displays the number of binary outputs reported by this RTU. This value will
increment with the addition of each configured Binary Output point. The maximum number of points
is 9999. The maximum number of actual points will depend on the memory available in the
controller.
The Starting Address parameter specifies the starting DNP address of the first Binary Output point.
The Allow Duplicate Modbus Addresses checkbox determines if the Modbus I/O database
addresses assigned to the DNP data points must be unique. Check this box if you want to allow more
than one point to use the same Modbus address.