d. Enter a value of 1 for First Point. This is the DNP Address of the first Binary Input point in
Station 10.
e. Enter 3 for Number of points to map.
f. Enter 11001 for First Register (First Modbus Register) address. Note that Modbus address
11000 must exist the in your controller database.
CAUTION: In a practical setting, a DNP Master may have local I/O mapped also
mapped to points within its DNP database. Ensure that you are not mapping
outstation DNP points to local address being used by local I/O.
The completed dialog should look like this:
g. Click on OK to add this entry to the Address Mapping table.
h. Use the DNP Master Status dialog, to confirm that remote points are being mapped to local
Modbus registers as shown below:
You can also confirm that remote points are being mapped to Modbus registers by monitoring the
status of Modbus registers 11001, 11002 and 11003.
How to Configure SCADAPack DNP Mimic Master
In addition to all the configuration procedures for a DNP Master, following the steps below to enable
the DNP Mimic master.
From the Controller menu, select DNP Configuration
1. Follow all steps in the Section 0 to configure the DNP master.
2. Click on the Master tree node.
3. Enable Mimic Mode.