ASCII Protocol Parameters
The TeleBUS ASCII protocol is an seven bit character based protocol. The table below
shows possible and recommended communication parameters.
Parameter
Possible Settings
Recommended Setting
Baud Rate
see Baud Rate section below
see Baud Rate section below
Data Bits
7 data bits
8 data bits
7 data bits
Parity
None
Even
Odd
none
Stop Bits
1 stop bit
2 stop bits
1
1 stop bit
Flow Control
Enabled
Disabled
disabled
Duplex
see Duplex section below
see Duplex section below
1
Not applicable to SCADAPack 330 or SCADAPack 350 controllers.
NOTE: Flow control should never be enabled with modems or in noisy environments. Noise
can result in the accidental detection of an XOFF character, which shuts down
communication. Flow control is not recommended for any environment, but can be
used on high quality, full duplex, direct wiring where speeds greater than 4800 baud
are required.