User manual

IEC61131 User and Reference Manual
April 22, 2008
361
Outputs
Type
Description
status
Integer
Status code returned from last set operation
0 = valid entry
1 = index for entry is out of range
2 = no translation (A and B entries are equal)
3 = invalid serial port
4 = invalid station address
5 = entry already defined
Notes
Refer to the TeleBUS Protocols User Manual for further information on Store and Forward
messaging.
Com3 is supported only when the SCADAPack Lower I/O module is installed. Com4 is
supported only when the SCADAPack Upper I/O module is installed.
Store and forward messaging is enabled on the required serial ports using the setprot
function.
See Also
getsf, clearsf