275
getled
minutesToDefault
LEDsDefaultState
Arguments
Inputs This function block has no inputs.
Outputs
Type
Description
LEDsDefaultState
Boolean
The LED default state is ON when TRUE.
The LED default state is OFF when FALSE.
minutesToDefault
Integer
Time in minutes to return to the default state, 1 to 65535
minutes.
See Also
setled
getmbip
Get Modbus IP Protocol Settings
The getmbip function is used to obtain the configured settings for a Modbus IP protocol.
This function block is used by the SCADAPack 330,SCADAPack 350 and SCADAPack 32
controller series only.
port
mstrIdleTimeout
getmbip
statusOfServer
srvrIdleTimeout
typeProtocol
Q
Arguments
Inputs
Type
Description
typeProtocol
Integer
Modbus IP Protocol
1 = Modbus/TCP
2 = Modbus RTU over UDP
3 = Modbus ASCII over UDP
Outputs
Type
Description
statusOfServer
Integer
1 = server for this protocol is enabled
0 = server for this protocol is disabled
port
Integer
Port for selected protocol type
mstrIdleTimeout
Integer
The length of time, in seconds, that a master