User manual

IEC61131 User and Reference Manual
April 22, 2008
218
The 5606 I/O Module provides 8 internal digital inputs, which indicate if the corresponding
analog input is in or out of range.
Digital Input channel 32 returns the status of AIN channel 0.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 33 returns the status of AIN channel 1.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 34 returns the status of AIN channel 2.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 35 returns the status of AIN channel 3.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 36 returns the status of AIN channel 4.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 37 returns the status of AIN channel 5.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 38 returns the status of AIN channel 6.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
Digital Input channel 39 returns the status of AIN channel 7.
OFF = AIN 0 is OK.
ON = AIN 0 is over or under range.
DOUT Sub Module
The DOUT sub-module module provides sixteen I/O channels for the digital outputs of the
SCADAPack 5606 I/O hardware. Data for each of the I/O channels may be connected to
user-defined variables with the I/O connection editor. The SCADAPack 5606 I/O hardware
digital outputs are updated continuously with data read from the variables.
The 5606 I/O Module provides sixteen digital outputs. These are relay outputs.
Digital Output channels 0 to 15 set the digital output status for the 5606 I/O Module.
0 = OFF (led off).
1 = ON (led on).
I/O Connection
Module address
This module is assigned a unique module address between 0
and 7. A maximum of eight SCADAPack 5606 I/O type modules
may be added to a system.
Library type
IO complex equipment
AIN sub-module
Data type
Integer / real
Channel type
Input
Number of channels
8
AOUT sub-module