User manual
IEC61131 User and Reference Manual
April 22, 2008
158
cntr5410
Counter input module 5410
Description
The cntr5410 I/O module provides four I/O channels for 5410 High Speed Counter Input
hardware. Data for each of the four I/O channels may be connected to user-defined
variables with the I/O connection editor. Connected variables are updated continuously with
data read from the counter inputs.
Set the cntr5410 module_address to match the address switches on the 5410 High Speed
Counter Input hardware.
The maximum count is 4,294,967,295. Counters roll over to zero when the maximum count
is exceeded.
I/O Connection
Module address
This module is assigned a unique module address between 0
and 15. No other counter input-type module may use this
module address.
Library type
IO board
Data type
Integer / real
Channel type
Input
Number of channels
4
Notes
Refer to the 5410 High Speed Counter Input Module User Manual for further information.