Owner`s manual
TELECHIEF
®
SERIES TM2000 / TM4000 / TM6000 OWNER’S MANUAL
4.0 Installation Procedure
4.1 General Precautions
1. Observe all safety precautions when climbing or working on the machine.
2. Turn off the main power source of crane/machines before installation to avoid electric shock.
Lockout/Tagout the main power source.
3. Receiver must be installed as to not touch any part of the crane/machine or structure during the operation,
except for mounting provisions.
4. The receiver must be fastened securely via shock-proof mount provided.
5. Before installation, inspect the crane/machine’s safety devices and make sure everything is in proper
working condition.
6. To avoid any interference, the receiver must be located away from motors, frequency drives, and power
cables (Section 4.3).
7. Coil suppressors are recommended on all contactor coils and relay coils. Control Chief
recommends RC type suppressors (Control Chief part number 0700-8002).
8. In outdoor applications make sure all case fasteners are tightened firmly. The recommended torque
setting is 35-40 inch-pounds. Make sure cord grip is secure. If the receiver is mounted with the antenna
facing sideways or upwards, wiring pigtail must be positioned with a drip loop. See illustration for preferred
mounting.
XXXXXXXXXXXX
XXXX
XXXX
XXXX
XXXXX
XXXXXXX
Drip Loop
Drip Loop
Case Fasteners x4
Cord Grip
Case Fasteners x4
Cord Grip
4.2 Receiver Preparation
4.2.1 Power Supply Selection
There are two types of power voltage (DC and AC) available for the TeleChief
®
Series:
DC Type
Input voltage: 12~24VDC. Wire + DC to Power 1 (black) and DC - to Power 2 (white).
Relay Contact: 15A-32VDC
AC Type (3 different transformers: 48/110V, 110/220V, 220/380V)
The voltage selection jumper is:
LOW HI
1. AC 48 / 110 V
Transformer 48V 110V
2. AC 110 / 220 V
Transformer 110V 220V
3. AC 220 / 380 V
Transformer 220V 380V
1. Locate the Hi/Low jumper to the lower left of the transformer.
2. Place the jumper connecting the two pins to enable the correct transformer setting as shown in
the chart above.
Note:
The default transformer is the 48V/110V version and jumper is normally set on Hi. Please contact
your distributor for other options and lead-times.
95-00-0-036 Rev D 6 Control Chief Corporation