requiring the more complex programming logic tied to timers and button Press / Release
events.
Note: When programming using double and triple-tap events, be aware that Press and
Release events also occur when double and triple-tap events occur. Plan your
programming using these events so that they don't conflict with the intended outcome. In
most cases, when using double and triple-tap programming events, don't program on the
Press and Release events.
• Network
• Added a new Network Tools menu. We replaced the Network Status menu with enhanced
functionality including tree views.
• System Remote Control. Added programming events to the System Remote Control SR-
150 and SR-250 ‘Watch’ and ‘Listen’ button presses. This lets the Installer use Control4
programming to define room-specific behavior when the Watch / Listen buttons are pressed.
The Watch / Listen button options now include: ‘No Action’ (new – used for programming
your own behavior), ‘Select Most Recently Used Device,’ and ‘Show Device List.’ You can
select the desired behavior using the Composer Pro System Design view. Programming
triggered by the Watch and Listen buttons is performed using the room events.
• Thermostat
• Undershoot/overshoot configuration now applies to both heat and cool. With the updated
Thermostat firmware, the ‘undershoot’ and ‘overshoot’ settings are now used to determine
when the Thermostat will call for heating and cooling.
Previously, the overshoot setting was only used for determining when to disengage the
heat, and the undershoot setting was only used for determining when to disengage the air
conditioning.
With Release 1.8.0, the undershoot setting determines when both the heating and cooling
systems are engaged, and the overshoot setting determines the cutoff for when the heating
and cooling systems are disengaged.
Examples:
Heating – Set point set to 72. With an undershoot of 1, the heater will engage at 71
degrees. With an overshoot of 1, the heater will cut off at 73 degrees.
Cooling – Set point set at 78. With an undershoot of 1, the cooler will engage at 79
degrees. With an overshoot of 3, the cooler will cut off at 75 degrees.
• Third-Party devices. The following third-party devices are no longer documented in Control4
documentation. Refer to Release 1.8 and earlier about configuration information for these
devices.
• VLinx Serial Server. Appendix C: Configuring Devices, "Add a VLinx Serial Server to
Expand Serial Control" has been removed from the Composer Pro User Guide and online
Help.
• HVAC devices.