User guide

Composer Pro User Guide
Copyright © 2012 Control4. All Rights Reserved.
200-00005 Composer Pro
User Guide Part 1
Page 100 of 199
Temperature CalibrationUse the up or down arrows to set x degree(s), and then click
Set Calibration. This lets you fine tune the current temperature reported by the Thermostat
by +/- 5 degrees. Example: If your Thermostat reads 72 degrees Fahrenheit, and you
determine that the current temperature should be 70 degrees Fahrenheit, press the down
button two times to lower the Thermostat’s reading to 70 degrees Fahrenheit. Click Set
Calibration.
Note: No changes to calibration should be made within 20 minutes of powering on the
Thermostat. The Thermostat generates a small amount of heat which affects the
calibration. After 20 minutes of continuous operation, this will stabilize allowing proper
calibration.
Heating Cutoff PointUse the up or down arrows to set x degree(s) from the set point,
and then click Set Heat Cutoff. This sets how far over the setpoint you want the heating
system to remain engaged before shutting off. Example: If the heat set point is set to 68
degrees Fahrenheit and the cutoff point is set to 2 degrees Fahrenheit, the heating system
will engage until reaching 70 degrees.
Cooling Cutoff PointUse the up or down arrows to set x degree(s) from the set point,
and then click Set Cool Cutoff. This sets how far under the setpoint you want the cooling
system to remain engaged before shutting off. Example: If the cool setpoint is set to 68
degrees Fahrenheit and the cutoff point is set to 2 degrees Fahrenheit, the cooling system
will engage until reaching 66 degrees.
Stage Minimum Off Time (Minutes)Use the up or down arrows to set the minimum off
time in minutes. Note: This setting takes effect as soon as the Advanced Device
Configuration box is closed.
This is the minimum amount of time that the heating or cooling will remain off before
initiating again. Example: If while cooling, the temperature does not reach the designated
cutoff point before the maximum run time is reached, the cooling system will shut off and
not initiate cooling again until the Minimum Off Time is reached. Note: Some HVAC