Instruction Manual

A-2
Status Outputs: Open-Collector Driver (ULN2003)
(50 VDC max, 200 mA continuous, 500 mA peak)
Optically Isolated
Drive Enable
Alarm
Speed Command: 0 to 10 VDC
Span Pot Adjustable, 5 to 12 VDC
Optically Isolated
Aux Supply: +5VDC + 5%
150 mA, Max
non-isolated
Serial Interface: RS485
300 to 9600 Baud
Full parameter access and control
Power Requirements: 115 +15% VAC (model # 3200-1931)
230 +15% VAC (model # 3200-1932)
50/60 Hz
0.1 Amp
Line Loss: 70 mSec ride through
Operating Temperature: 0° to 55° C Int. Enclosure
0° to 40° C Ext. Enclosure
Storage Temperature: -25° to 70° C
Humidity: 0 to 95%, non-condensing
Physical Dimensions: 4.0 inches height
4.0 inches width
6.0 inches depth (Interior Panel)
Faceplate Rating: Nema 4, 4X, 12, 13
IP65
Environment: The ML–Trim shall be installed in a pollution
degree 2 macro - environment
Altitude: To 3,300 Feet (1000 meters)
Weight: 49 ounces