Datasheet

WNMB-11.20.17: Specications are subject to change
2150 Miller Drive, Suite A • Longmont CO 80501 • USA
sales@ctlsys.com • www.ctlsys.com
(888) 928-8663 • Fax (303) 444-2903
Quantities Measured
True RMS Power: watts, per phase and sum
Reactive Power: VARs, per phase and sum
Power Factor: Phase, per phase and average
True RMS Energy: kWh per phase and sum
Reactive Energy: VAR hours, sum
Frequency
RMS voltage per phase
RMS current per phase
Demand and peak demand
Accuracy
0.5% nominal (see manual for details)
Electrical
Operating Voltage Range: 80% to 115% of nominal
Power Line Frequency Range: 50 to 60 Hz
Environmental
Operating Temperature: -30°C to +75°C (-22°F to 167°F)
Humidity: 5 to 90% RH (non-condensing)
Mechanical
Enclosure: high impact, ABS plastic
Flame Resistance Rating: 94V-0, IEC FV-0
Size: 5.63” × 3.34” × 1.5” (143mm × 85mm × 38mm)
Weight: 10.8 oz (305 gm)
Connectors: euroblock style pluggable terminal blocks
Modbus Communication
EIA RS-485 interface
Baud Rates: 9,600, 19,200 and 38,400 (Opt 38K)
Duplex: half (two-wire plus common)
Parity: N81 (no parity, eight data bits, one stop bit)
E81 (even parity, Opt EP)
Modbus Buffer: 256 bytes
Response Time: 5 to 300 milliseconds
Regulatory
FCC Class B, EN 55022 Class B
UL and cUL Listed (UL 61010-1)
CE Mark and RoHS compliant
Immunity: EN 61326, (industrial locations)
WATTNODE
®
MODBUS
WattNode® Wiring Diagram, Three Phase Example
Accu-CT® Split-Core CTs
Safe, low voltage output, 0.333 Vac
Primary Ratings: 5 to 600 amps,
600 Vac, 50 or 60 Hz
UL & cUL, CE, RoHS compliant
0.75” and 1.25” opening
High accuracy options C0.6, C0.3
Standard Split-Core, Solid-Core
and Bus Bar Series CTs
Safe, low voltage output, 0.333 Vac
Multiple Models: 5 to 6000 amps,
600 Vac, 50/60 Hz nominal
UL & cUL, CE, RoHS compliant
Custom sizes available
Rogowski CTs
Safe, low voltage output, 0.333 Vac
Multiple Diameters: 3.1", 4.5", 7.5", 12"
Primary Ratings: 250 to 6000 amps