Specifications

T4.7
Contactors
Type
CTX 24
CTX 40
CTX 63
1 current
path
24.0 A
21.0 A
17.0 A
7.0 A
0.9 A
40.0 A
23.0 A
18.0 A
8.0 A
1.0 A
50.0 A
25.0 A
20.0 A
9.0 A
1.1 A
3 current
paths series
24, 0 A
24.0 A
24.0 A
24.0 A
13.0 A
40.0 A
40.0 A
40.0 A
30.0 A
15.0 A
63.0 A
63.0 A
60.0 A
33.0 A
17.0 A
2 current
paths series
24.0 A
18.0 A
14.0 A
6.5 A
1.0 A
40.0 A
20.0 A
16.0 A
7.0 A
1.1 A
44.0 A
22.0 A
18.0 A
8.0 A
1.2 A
T4
Lamp type
Incandescent lamps
Fluorescent lamps
High presure mercury
vapor lamps
eg. HQL, HPL
Lamps with electronic
power supply units
In (A)
0.26
0.43
0.87
1.3
2.17
4.35
0.35
0.37
0.43
0.54
0.67
1.5
1.5
2x0.13
2x0.22
2x0.24
2x0.34
2x0.65
2x0.75
0.11
0.13
0.22
0.24
0.65
0.65
0.75
0.61
0.8
1.15
2.15
3.25
5.4
7.5
8
0.28
0.41
0.65
1.22
1.95
3.45
4.8
5.45
CTX 24
25
15
7
5
3
1
30
26
20
16
12
5
5
2x26
2x20
2x16
2x12
2x5
2x5
8
7
8
6
5
2
2
14
10
7
4
2
1
1
1
5
4
3
2
1
-
-
1
24
18
16
11
14
8
CTX 63
83
50
25
16
10
5
155
140
105
85
60
28
28
2x140
2x105
2x85
2x60
2x28
2x28
67
60
67
50
43
17
17
50
38
26
14
10
6
4
4
43
37
26
15
10
5
4
2
76
48
47
29
46
24
Rated
operational
voltage Ue
24 VDC
48 VDC
60 VDC
110 VDC
220 VDC
24 VDC
48 VDC
60 VDC
110 VDC
220 VDC
24 VDC
48 VDC
60 VDC
110 VDC
220 VDC
DC-1 (L/R 1ms)
2 current
paths series
24.0 A
24.0 A
24.0 A
16.0 A
4.5 A
40.0 A
40.0 A
32.0 A
17.0 A
5.0 A
63.0 A
43.0 A
35.0 A
19.0 A
5.5 A
3 current
paths series
24.0 A
24.0 A
24.0 A
16.0 A
4.0 A
40.0 A
40.0 A
34.0 A
18.0 A
4.5 A
63.0 A
47.0 A
38.0 A
21.0 A
5.0 A
1 current
path
16.0 A
8.0 A
4.0 A
1.6 A
0.2 A
19.0 A
10.0 A
5.0 A
1.8 A
0.3 A
21.0 A
11.0 A
5.5 A
2.0 A
0.3 A
Switching of DC (table 2)
DC-3 (L/R 2ms)
Watt
60
100
200
300
500
1000
15
20
40
42
65
115
140
2x20
2x40
2x42
2x65
2x115
2x140
15
20
40
42
65
115
140
50
80
125
250
400
700
1000
2000/400V
50
80
125
250
400
700
1000
2000/400V
1x18
2x18
1x36
2x36
1x58
2x58
CTX 20
21
13
7
4
3
1
25
22
17
13
10
4
4
2x22
2x17
2x13
2x10
2x4
2x4
6
5
6
4
4
1
1
12
7
5
3
1
-
-
-
4
3
2
1
-
-
-
-
15
8
12
7
11
6
CTX 40
54
32
16
11
6
3
100
85
65
52
40
18
18
2x85
2x65
2x52
2x40
2x18
2x18
15
14
15
12
10
4
4
36
27
19
10
7
4
3
3
10
8
6
3
3
1
1
2
55
34
34
20
32
17
F)
4.5
5
4.5
6
7
18
18
7
8
10
18
25
45
60
35
Permitted number of lamps per phase (230 V, 50 Hz) for contactor typeLamp data Capacitor
Switching for lamp load (table 3)
uncompensated and series compensation
two-lamp circuit
parallel compensation
uncompensated
parallel compensation
Permitted number of electropower supply units per phase