Specifications

> 3 2 <
>
ENERGY METER ACCESORIES / LOAD MANAGER
> MER - DOMOTAX ORBITAX Accessories
ENERGEST 6051
Optical reader
This provides the option to easily connect a portable reader unit to the measu-
r
ing equipment. The optic-coupling can be quickly, easily and safely carried out
for the user using a computer USB port and connecting the optical reader to the
meter optical port.
Modem ORBITEL RS232 / ORBITEL RS485
Allows remote reading and import of data from a meter with RS32 or RS485 port
by GSM Modem. Consists of: PC connection cable, antenna, meter connection
cable, modem and power supply.
*
T
he operation of the equipment is subject to the characteristics of the GSM communica-
tion of the country. Consult.
RS232 to RS485 adapter
This permits the conversion of an RS232serial port into RS485 for reading seve-
ral meters simultaneously. It includes a PC or modem RS-232 connection cable
RS232-RS485 converter and power supply cable.
RS232/RS485 adapter to Ethernet and
RS232/RS485 adapter to radiofrequency
T
his is an assembly for reading a meter with RS-232 output or a meter network
with RS-485 output over an Ethernet 10/100 Base TX network. It can be installed
on a DIN rail or surface. Industrial grade.
It works over a LAN and the Internet (TCP/IP).
The radiofrequency RS232/RS484 adapter allows remote reading of a meter net-
work by frequency, i.e. without the need for complex wired network.
Read software
ITACA T3: automatic read software for ORBITAX T3.
AGNI: programmed read software for ORBITAX T3.
DOMOTAX: read software for DOMOTAX.
ENERGEST 6051 is a load management solution. Two
relays control load activetion and deactivetion in func-
tion of general consumption and the maximum power
set point established by the user. It is very useful for
heating control divided into three sections, to prevent
exceeding the contracted maximum power and gua-
ranteeing 100% accumulator load. It also permits the
display of current, voltage, active power, reactive
power, cos
j, active energy and frequency.
Rated voltage
Ib base current, (I maximum)
Current measure
Switching capacity
Relay functions
Accuracy
Display
Protection type
Installation
230 Va.c. / 50-60 Hz
60 A
By means of transformer
2 x 2 A 250 Va.c.
NO/NC configuration
Current reference value
Hysteresis value
Load activetion delay
Sample period to
connect the load
Voltage 0, 5%
Current 1%
Power 2%
Frequency ±0, 1 Hz
Active energy class 2
Back light LCD display
IP 20 / IP 51 in front
DIN rail (4 modules)
> Features> Description
> Connection diagram> Dimensions
Weight: 437 gr.