Data Sheet
8
X-2017, www.findernet.com
I
14 SERIES
Electronic staircase timers16A
14
SERIES
Functions
Type 14.01 Functions selectable with front rotary selector
(BE) Staircase timer
On initial impulse the output contact closes and timing starts for the pre-set duration;
subsequent impulses during the timing period will extend the timing period by the full
pre-set value.
On expiry of the time delay, the output contact opens.
BE
+
(ME) Staircase timer + Staircase maintenance
In addition to the Staircase timer function (BE), an impulse of ≥5seconds will close
the output contact for 60minutes, after which time the contact will open. Ideal for
maintenance or cleaning activities. The 60minute timing can be interrupted by a further
impulse of ≥5seconds, and the output contact then opens
(BP) Staircase timer with early warning
On initial impulse the output contact closes and the timing starts for the pre-set duration.
After the timing period, the output contact blinks off once; 10secs later the contact blinks
off twice, and after a further 10secs the contact opens.
During the pre-set and 20 second warning time, it is possible, by a further impulse, to
extend the time by the full pre-set value.
BP
+
(MP) Staircase timer with early warning + Staircase maintenance
In addition to the Staircase timer function (BP), an impulse of ≥5seconds will close the output
contact for 60minutes, after which time the contact will open. Ideal for maintenance or
cleaning activities. The 60minute timing can be interrupted by a further impulse of ≥5seconds,
and the output contact then opens
(IT) Timing step relay
On initial impulse the output contact closes and timing starts for the pre-set duration; On
expiry of the time delay, the output contact opens.
During the timing period it is possible to immediately open the contact with a further impulse.
(IP) Timing step relay with early warning
On initial impulse the output contact closes and timing starts for the pre-set duration;
After the timing period, the output contact blinks off once; 10 secs later the contact blinks
off twice, and after a further 10 secs the contact opens.
During the pre-set and 20 second warning time, it is possible to immediately open the
output contact by a further impulse.
(RI) Step relay
After every impulse, the output contact changes state - alternately switching from open to
closed and vice versa.
Light ON
With this function set - the output contact stays permanently closed.
NOTE: The blinking within the Early Warning functions (BP and IP) could cause re-start problems for fluorescent lamps with electromagnetic chokes
(both conventional and compact types); We consequently suggest not to use such lamps with these functions.