Users Manual

Page | 16
FIGURE 8 depicts a “Split-Bolt Connector” or “Split-Bolt Bug”. Multiple manufacturers offer
equivalent products.
1
2
3
FIGURE 8
1. “Main” or “run” conductor, referring to the existing load side service entrance
neutral conductor within the meter socket. Often there is no need to disconnect the
existing wire provided there is enough slack to manipulate the conductor.
2. Tap conductor, in this case the ConnectDER neutral pigtail would be terminated
here.
3. Pressure bar that separates the run and tap conductors. This makes it possible to
splice aluminum (often the residential service entrance cable is aluminum) to
copper.
Check to see that the connector you select is
available in sizes to accommodate the correct range of run and tap conductors
suitable for use for either copper or aluminum conductors
UL listed or otherwise approved by the utility and AHJ.
If a neutral pigtail other than the furnished AWG size is required, it must be
furnished by the installer. Wire terminations at the ConnectDER must be made with
copper conductors only.
WARNING Install this and other neutral termination options in
accordance with the manufacturer’s instructions.