Users Manual

Page | 15
Possible options for connecting the neutral pigtail to the meter socket, in case there is no
spare terminal as shown in FIGURE 6 (previous page):
Connect the end of the neutral wire pigtail lead to the load side grounded neutral
conductor. Use a suitable Listed pressure connector such as a gutter tap, split bolt
connector, or parallel groove clamp. More detail about each is provided below.
These suggestions are not intended to be a full listing of options, and ConnectDER does not
endorse one particular method over another. Consideration should be given to routing and
securing the wiring in such a way that it is protected from non-insulated live parts.
If a neutral pigtail other than the furnished AWG size is required, it must be
furnished by the installer. Wire terminations at the ConnectDER must be made with
copper conductors only.
WARNING Install this and other neutral termination options in
accordance with the manufacturer’s instructions.
FIGURE 7 depicts a “Parallel Tap Connector” or “Gutter Tap Connector”. Multiple
manufacturers offer equivalent products.
1
2
FIGURE 7
1. Removable component for the “main” or “run” conductor, referring to the existing
load side service entrance neutral conductor within the meter socket. Often there is
no need to disconnect the existing wire provided there is enough slack to
manipulate the conductor.
2. Termination point for the “tap” conductor, in this case the ConnectDER neutral
pigtail.
Check to see that the connector you select is
available in sizes to accommodate the correct range of run and tap conductors
suitable for use for either copper or aluminum conductors
available with an insulating cover if required
UL listed or otherwise approved by the utility and AHJ.