Users Manual
Page | 14
INSTALL THE NEUTRAL LEAD
4-JAW METER SOCKET
WARNING All 4-jaw meter sockets require a neutral conductor pigtail
to be attached from the rear of the ConnectDER to a neutral
point inside of the meter socket.
Before beginning, make sure that the ConnectDER circuit breaker is open (OFF).
FIGURE 6 below depicts the inside of a typical 4 jaw meter socket.
This model has a single accessory position, circled in red. Many sockets have a second
accessory position, depicted below as a blue dot. If these accessory positions are not in use
(such as for a grounding electrode conductor), they are the preferred option for securing
the neutral connection. These accessory positions may contain pressure terminal(s) or
hardware for the connection of compression (ring) terminals. Terminate in accordance
with the marked torque values or per the terminal manufacturers specifications. Potential
alternatives are suggested on the next page if these are not available.
FIGURE 6