REMOVE THE METER AND METER SOCKET COVER
WARNING
Contact the utility for specific information on their standard practices and/or to schedule a
visit by utility or utility-authorized personnel to remove the meter.
FIGURE 5
Remove the utility tamper-prevention seal(s).
1. Remove the locking ring (for ring-type meter sockets).
2. Remove the electric meter as shown in FIGURE 5.
3. Inspect the meter socket terminals for damage such as loose or broken wires,
damaged jaws, etc.
The ConnectDER may be installed in meter sockets of any age, provided:
The meter socket and service entrance conductors are in good condition and comply
with utility requirements and local codes.
The minimum work space clearances (as specified by the serving utility) are
maintained after the ConnectDER is installed.
The 5
th
jaw has sufficient ampacity or there is satisfactory means to terminate the
neutral pigtail. A neutral pigtail is required for all 4-jaw meter sockets.
ConnectDER use in shallow “button” type meter sockets is not recommended.
Temporarily block off all energized parts with appropriate insulating material or insulating
device. Set the ConnectDER circuit breaker to the OFF position. This ensures the field
wiring terminals will be de-energized after inserting the ConnectDER into a live meter
socket.