Operating instructions

3 / 16
EN-TraceTekTTTS12-IM-H8085601/15
THERMAL BUILDING &
INDUSTRIAL HEAT TRACING SOLUTIONS
INSTALLATION ITEMS NOT SUPPLIED
• Wall fasteners for surface mounting (four screws) appropriate to the wall surface material
• (Optional) TT-TS12 TRIM FLANGE Part Number P000000780 (available for semi-flush mounting of the TT-TS12-Panel)
TOOLS REQUIRED:
Drills and chassis punch for electrical conduit or cable gland entries into TT-TS12-Panel at desired locations
Center punch
Phillips (cross-head) screwdriver
Small flat-head screwdrivers for terminal block connections
Large flat head screwdriver (or coin) to operate door latch
Wire cutter and stripper for field wiring connections
Long handle 4mm T-Bar Allen wrench
STORAGE:
Keep the TT-TS12-Panel in a dry place prior to installation to avoid possible damage to internal components
TT-TS12-Panel General Information:
Power Requirement 100 to 240 Vac; 50/60 Hz (A separate 15 Amp Branch Circuit with dedicated Circuit Breaker is required)
Weight 11.8kg (26.0 lb) (typical with 4 SIM’s installed)
Dimensions (W x H x D) 431.8 mm x 330.2 mm x 152.4 mm (17.0 in x 13.0 in x 6.0 in)
Power consumption 40 W (typical with 4 SIM’s installed)
Built-in relays 3 SPDT Pre-assigned (Buzzer Control, LEAK, and TROUBLE); 1 SPST Pre-assigned (Watchdog)
1 SPDT; 3 SPST User Programmable Relays
Additional channel specific relays available if TTSIM-1A units are installed
Rating: 5 A at 250 Vac or 5 A at 24 Vdc
External Relays: Expandable to 320 user programmed relays using TT-NRM-BASE and TT-NRM-2RO modules
Storage temperature –20°C to 60°C (-4°F to 140°F)
Operating temperature -20°C to 60°C (-4°F to 140°F)
Ingress Protection NEMA 1; IP 10
Approvals and Certifications: All internal components are UL Listed or Recognized. Panel is built and approved to UL 508A Standard.