Operating instructions

14 / 16
EN-TraceTekTTTS12-IM-H8085601/15
THERMAL BUILDING &
INDUSTRIAL HEAT TRACING SOLUTIONS
FINAL INSPECTION:
Check for:
No metal filings or other foreign materials present (vacuum or blow out)
Back plane assembly hold down bolts are tight
Mounting hardware tight
Conduit or cable glands tightened
All screw connections at terminal blocks snug (do not over tighten smaller screw terminals)
All wires routed such that the door opens and closes freely
All wire duct covers replaced
Leader cables from sensor circuits identified
Generally neat and organized appearance
Fuses installed in terminal block fuse holders at mains power connection point (lower right corner of back plane assembly)
APPLY POWER:
Ensure that fuse holders at mains power connection terminal block are properly seated. Apply mains power at circuit breaker panel.
(Note that the fuses in the TT-TS12-Panel mains power connection terminal block are designed to act as local disconnect for panel
servicing).
Observe any installed TTSIM units for successful power on indications:
TTSIM-1 indication is a red LED that blinks once every 10 seconds to indicate power and CPU activity
TTSIM-1A has a green power on LED that blinks once every 5 seconds to indicate power and CPU activity.
CLOSE AND SECURE THE DOOR LATCH:
Observe the front screen of the TT-TS12 touchscreen for boot-up sequence. This process will take about 1 minute and the screen
may go dark or appear to pause for several seconds from time to time during a normal start-up. Proper start up is indicated by a
screen like that shown below, however the number and type of TTSIM may be different than what is shown in this example.