Operating instructions

12 / 16
EN-TraceTekTTTS12-IM-H8085601/15
THERMAL BUILDING &
INDUSTRIAL HEAT TRACING SOLUTIONS
ii. Lift the ADAM-4522 module out of the way to expose the ADAM 4069 module beneath.
iii. The ADAM-4069 module has 4 available Form-A (SPST) Normally Open relays available and 1 Form-C (SPDT) terminal
strips on the top and bottom connector. Relays 4,5 and 6 are Form-A; relay 7 is Form-C
iv. The connectors are removable for easier wiring.
v. Make relay connections as appropriate. The watchdog signal is between RL3 NO and RL3 COM.
vi. Reinstall ADAM-4522 module on top of ADAM-4069 module and secure screws.
7. Ethernet Connections
a. The TT-TS12 has two RJ-45 Ethernet/LAN connector sockets on the rear of the TT-TS12 touch screen.
b. Use standard network cables to connect the TT-TS12 to the local LAN for: email alarm notification, remote screen viewing and
operation via VNC, Modbus/TCP and future network services.
c. There are no terminal blocks or LAN connections on the back plane, so make the Ethernet connections the last field wiring step
and leave sufficient slack to run from the conduit entries to the rear of the TT-TS12 touchscreen as mounted on the door panel.
d. Take care when closing the enclosure door to avoid pinching the LAN cable.