Instruction manual
2
1–2 Ordering Code
Data Communication Accessories:
TEC99001 Smart Network Adapter for third party SCADA software
which converts 255 channels of RS-485 or RS-422 to RS-
232 Network.
TEC99003 Smart Network Adapter for connecting the programming
port to the RS-232 PC serial port. Allows downloading and
reading of configuration information directly from a person-
al computer. Can be used with TEC-4100, TEC-7100, TEC-
8100 and TEC-9100.
TEC99030 "Tempco Config Set" PC software for use with TEC99003
Smart Network Adapter. (can be downloaded at no charge
from www.tempco.com)
Minimum System Requirements:
Microsoft Windows 2000, 98, 95, NT4.0
Pentium 200 MHz or faster
32 MB RAM (64 MB recommended)
Hard disk space: 2 MB
TEC99011 Programming port cable for TEC-4100, TEC-7100, TEC-
8100 and TEC-9100. Connects the controller to the
TEC99003 Smart Network Adapter.
Power Input
4 = 90-250 VAC
5 = 11-26 VAC/VDC
9 = Other
Signal Input
Universal, can be
programmed in the field
for item 5 or 6
5
= TC: *J,K,T,E,B,R,S,N,L
0
-60 mV
6 = RTD: *PT100 DIN,
PT100 JIS
7 = 0-1 VDC
8 = *0-5, 1-5 VDC
A = 0-10 VDC
B = *4-20, 0-20 mA
9 = Other
*indicates default value
Output 1
1 = Relay: 2A/240 VAC
2 = Pulse dc for SSR drive:
5 Vdc (30 mA max)
3 = Isolated, 4-20 mA (default)
0-20 mA
4 = Isolated, VDC, 1-5 (default)
0-5, 0-1
5 = Isolated, VDC, 0-10
6 = Triac-SSR output
1A/240 VAC
C = Pulse dc for SSR drive:
14 Vdc (40 mA max)
9 = Other
Output 2
0 = None
1 = Relay: 2A / 240 VAC
2 = Pulse dc for SSR drive: 5 Vdc (30 mA max)
3 = Isolated, 4-20 mA (default), 0-20 mA
4 = Isolated VDC, 1-5 (default), 0-5, 0-1
5 = Isolated VDC, 0-10
6 = Triac-SSR output 1A / 240 VAC
7 = Isolated 20V @ 25 mA DC, Output Power Supply
8 = Isolated 12V @ 40 mA DC, Output Power Supply
9 = Isolated 5V @ 80 mA DC, Output Power Supply
C = Pulse dc for SSR drive: 14 VDC (40 mA max)
A = Other
P
ower Input
4 = 90-250 VAC
5 = 11-26 VAC/VDC
9 = Other
Signal Input
Universal, can be programmed in the field
for item 5 or 6
5
= TC: *J,K,T,E,B,R,S,N,L 0-60mV
6 = RTD: *PT100 DIN, PT100 JIS
7 = 0-1 Vdc
8 = *0-5, 1-5 VDC
A = 0-10 VDC
B = *4-20, 0-20 mA
9 = Other
*indicates default value
Output 1
1 = Relay: 2A / 240 VAC
2 = Pulse dc for SSR drive: 5 VDC (30 mA max)
3 = Isolated, 4-20 mA (default), 0-20 mA
4 = Isolated, VDC, 1-5 (default), 0-5, 0-1
5 = Isolated, VDC, 0-10
6 = Triac-SSR output 1A/240 VAC
C = Pulse dc for SSR drive:14 VDC (40 mA max)
9 = Other
Output 2
0 = None
1 = Relay: 2A/240 VAC
2 = Pulse dc for SSR drive: 5 VDC (30 mA max)
3 = Isolated, 4-20 mA (default), 0-20 mA
4 = Isolated VDC, 1-5 (default), 0-5, 0-1
5 = Isolated VDC, 0-10
6 = Triac-SSR output 1A/240 Vac
7 = Isolated 20V @ 25 mA DC, Output Power Supply
8 = Isolated 12V @ 40 mA DC, Output Power Supply
9 = Isolated 5V @ 80 mA DC, Output Power Supply
C = Pulse dc for SSR drive: 14 VDC (40 mA max)
A = Other
Alarm
0 = None
1 = Relay: 2A / 240 VAC, SPDT
9 = Other
Communication
0 = None
1 = RS-485 Interface
2 = RS-232 Interface
3 = Retransmission 4-20 mA (default), 0-20 mA
4 = Retransmission 1-5 VDC (default), 0-5 VDC
5 = Retransmission 0-10 VDC
9 = Other
Case Options
0 = Panel mount standard
1 = Panel mount with NEMA 4X/IP65 front panel
2 = DIN rail mount
Alarm
0 = None
1 = Relay: 2A/240 VAC,
SPDT
9 = Other
Communication
0 = None
1 = RS-485 Interface
2 = RS-232 Interface
(not available for TEC-7100)
3
= Retransmission 4-20 mA
(
default), 0-20 mA
4 = Retransmission 1-5 Vdc
(default), 0-5 VDC
5 = Retransmission 0-10 VDC
9 = Other
NEMA 4X / IP65
0 = No
1 = Yes
TEC-4100-
TEC-7100-
TEC-8100-
T
EC-9100-