Instruction manual
13
The ON-OFF control may introduce excessive process oscillation
even  if  hysteresis  is  minimized.  If  ON-OFF  control  is  set  (i.e.,
PB=0), TI, TD, CYC1, OFST, CYC2, CPB, and DB will be hid-
den  and  have  no  function  in  the  system.  The  auto-tuning  and
bumpless transfer functions will be disabled as well.
Heat only P (or PD) control: Select REVR for OUT1, set TI to
0. OFST is used to adjust the control offset (manual reset). O1HY
is hidden if PB is not equal to 0. OFST function: OFST is meas-
ured  by  %  with  a  range  of  0–100.0%.  In  the  steady  state  (i.e.,
process has been stabilized), if the process value is lower than the
set point by a definite value, say 5°C, while 20°C is used for PB,
that is lower by 25%, then increase OFST 25%, and vice-versa.
After adjusting OFST value, the process value will be varied and
eventually coincide with set point.
Refer to section 3-12 “manual tuning” for the adjustment of PB
and TD. Manual reset (adjust OFST) is not practical because the
load may change  from  time  to  time  and  OFST may  need  to  be
adjusted repeatedly. PID control can avoid this situation.
Heat only PID control: If REVR is selected for OUT1, PB and
TI should not be zero. Perform auto-tuning for the new process,
or set PB, TI, and TD with historical values. See section 3-11 for
auto-tuning operation. If the control result is still unsatisfactory,
then use manual tuning to improve control. See section 3-12 for
manual tuning. The unit contains a very advanced PID and Fuzzy
Logic algorithm to create a very small overshoot and very quick
response to the process if it is properly tuned.
Control Outputs, continued…
Heat only ON-OFF control: Select REVR for OUT1. Set PB
(proportional band) to 0. O1HY is used to adjust dead band for
ON-OFF control. The output 1 hysteresis (O1HY) is enabled
i
n case PB=0. The heat only on-off control function is shown
in the following diagram:
3.3 & 3.4 Alarm Figures, next page…
Cool only control: ON-OFF control, P (PD) control, and PID
c
ontrol can be used for cool control. Set OUT1 to DIRT (direct
action).  The  other  functions  for  cool  only  ON-OFF  control,
cool  only  P  (PD)  control,  and  cool  only  PID  control  are  the
same  as  for  heat  only  control  except  that  the  output  variable
(and action) for cool control is inverse to heat control.
NOTE: ON-OFF control may result in excessive overshoot and
undershoot  problems in  the  process. P (or  PD)  control will
result in  a  deviation  of process value  from  the set point. It  is
recommended to use PID control for heat-cool control to produce
a stable and zero offset process value.
Other  setup  required: O1TY,  CYC1,  O2TY,  CYC2,  O1FT
and O2FT are set in  accordance  with  the types of OUT1  and
OUT2 installed. CYC1 and CYC2 are selected according to the
output  1  type  (O1TY)  and  output  2  type  (O2TY).  Generally,
select  0.5~2  seconds  for  CYC1  if  SSRD  or  SSR  is  used  for
O1TY;  10~20 seconds  if  relay  is used  for  O1TY. CYC1  is
ignored if a linear output is used. Similar conditions are applied
for CYC2 selection.
You  can  use  the  auto-tuning  program  for  the  new  process  or
directly set the appropriate values for PB, TI, and TD accord-
ing to historical records for the repeated systems. If the control
behavior is still inadequate, use manual tuning to improve the
control. See section 3-12 for manual tuning.
CPB (Cooling Proportional Band) Programming: The cool-
ing proportional band is measured by % of PB with a range of
50-300.  Initially  set  100%  for  CPB  and  examine  the  cooling
effect. If the cooling action should be enhanced, then decrease
CPB, if the cooling action is too strong, then increase CPB. The
value of CPB is related to PB and its value remains unchanged
throughout the auto-tuning procedures.
Adjustment of CPB is related to the cooling medium used. If air
is used  as the  cooling medium, adjust CPB to 100%. If  oil is
used as the cooling medium, adjust CPB to 125%. If water is
used as the cooling medium, adjust CPB to 250%.
DB  (Heating-Cooling  Dead  Band)  Programming: The
adjustment of DB is dependent on the system requirements. If
a  more  positive  value  of  DB  (greater  dead  band)  is  used,  an
unwanted cooling action can be avoided but an excessive over-
shoot over the set point will occur. If a more negative value of
DB (greater overlap) is used, an excessive overshoot over the
set point can be minimized, but an unwanted cooling action will
occur. It is adjustable in the range -36.0% to 36.0% of PB. A
negative DB value shows an overlap area over which both out-
puts are active. A positive  DB  value  shows  a  dead  band  area
over which neither output is active.
Output  2  ON-OFF  control (alarm  function): Output  2 can
also be configured with an alarm function. There are four kinds
of alarm functions that can be selected for output 2. These are:
DE.HI  (deviation  high  alarm),  DE.LO  (deviation  low alarm),
PV.HI  (process  high  alarm), and  PV.LO  (process  low alarm).
Refer to figure 3.3 and figure 3.4 for descriptions of the devia-
tion alarm and the process alarm.










