Technical data
Download, testing and diagnostics
CPU 317T: Technology Functions
A5E00251798-03
8-7
Maximal shutdown delay
Here you enter the time for monitoring shutdown of the integrated technology. If the
integrated technology is not shut down after this time has expired, the Technology
CPU changes to STOP mode.
Number of tolerated IPO overflow events
An "IPO overflow" event occurs whenever the execution of the interpolator takes
longer than the configured interpolator cycle. In this case, the next interpolator is
ignored and thus not started within the selected cycle. It is started as usual if the
interpolator is executed within the current cycle.
Each ignored interpolator is counted as "IPO overflow". From the drop-down list,
select the number of tolerated successive "IPO overflows" after which the
Technology CPU goes into STOP.