Technical data
Technology DBs
CPU 317T: Technology Functions
A5E00251798-03
7-55
7.11.6 ErrorIDs - Cam technology DBs
Valid for firmware version V3.1.x of the integrated technology
Warnings
ErrorID
Warning message Possible causes To correct or avoid errors Interrupts in
S7T Config*
0020 Restart to apply
parameter changes
You have changed a
parameter which is not applied
directly
To apply the parameter changes,
you need to lock and reinitialize
the object (MC_Reset with
Restart = TRUE)
20010
0022 Internal warning Temporary internal problem For detailed information, refer to
the alarm view in S7T Config
40003
0027 Could not adhere to
interpolation
properties
Discontinuity of the position or
gradient was detected at the
transition between cam
segments
Move the interpolation limits.
Check the cam disk profile.
Change the criteria for the
interpolation of segments.
40008
* Interrupts in S7T Config, which may be associated with the indicated warning.
Error
ErrorID
Error message Possible causes To correct or avoid errors Interrupts in
S7T Config*
8001 Fatal internal error Faulty / inconsistent project /
software; can not be
influenced by the user.
Check the consistency of your
project data. Compile the data
again, then download all data to
the module. Evaluate the error
code in the alarm view of
S7T Config and inform the
Siemens Hotline.
20001
8002 Internal fault • Version conflict
• Firmware error
• Inconsistent software
Check the consistency of your
project data. Compile the data
again, then download all data to
the module. Evaluate the alarm
view of S7T Config and inform the
Siemens Hotline.
30004, 30005,
30010, 30011,
30015
8003 Fatal configuration
error
Faulty axis configuration data.
A hardware driver, or the
device it addresses, may not
be available
• Check the plausibility of
changed parameters.
(Example: Spindle pitch is
0;
Homing with absolute value
encoder above zero mark is
not possible).
• Check the connected devices
and their configuration in
HW Config.
• Verify that the telegram used
is compatible with the object.
• Reload the technology to the
PLC.
20004, 20006
8004 Configuration error The configuration of a
technological object is
incomplete or faulty.
Check the plausibility of changed
parameters. Evaluate the detailed
information in the alarm view of
S7T Config.
20003, 20011