Technical data

Technology DBs
CPU 317T: Technology Functions
7-52 A5E00251798-03
7.11.5 ErrorIDs - Measuring sensor technology DB
Valid for firmware version V3.1.x of the integrated technology
Warnings
ErrorID
Warning message Possible causes To correct or avoid errors Interrupts in
S7T Config*
0020 Restart to apply
parameter changes
Changes to a parameter are
not applied directly
To apply the parameter changes,
you need to lock and reinitialize
the object (MC_Reset with
Restart = TRUE)
20010
* Interrupts in S7T Config, which may be associated with the indicated warning.
Error
ErrorID
Error message Possible causes To correct or avoid errors Interrupts in
S7T Config*
8001 Fatal internal error Faulty / inconsistent project /
software; can not be
influenced by the user.
Check consistency of your project
data. Compile the data again,
then download all data to the
module. Evaluate the error code
in the alarm view of S7T Config
and inform the Siemens Hotline.
20001
8002 Internal fault Version conflict, firmware
error, inconsistent software
Check consistency of your project
data. Compile the data again,
then download all data to the
module. Evaluate the alarm view
of S7T Config and inform the
Siemens Hotline.
30004, 30005,
30010, 30011,
30015
8003 Fatal configuration
error
Faulty axis configuration data.
A hardware driver, or the
device it addresses, may not
be available
Check the plausibility of
changed parameters.
(Example: Spindle pitch is
0;
Homing with absolute value
encoder above zero mark is
not possible).
Check the connected devices
and their configuration in
HW Config.
Verify that the telegram used
is compatible with the object.
Reload the technology to the
PLC.
20004, 20006,
40006
8004 Configuration error The configuration of a
technological object is
incomplete or faulty.
Check the plausibility of changed
parameters. Evaluate the detailed
information in the alarm view of
S7T Config.
20003, 20011