Technical data
Technology DBs
CPU 317T: Technology Functions
A5E00251798-03
7-35
ErrorID
Error message Possible causes To correct or avoid errors Interrupts in
S7T Config*
8049 Illegal object
combination
Faulty combination of technology
objects. Examples:
• Axis_2 was set as leading
synchronization axis for
Axis_1, and Axis_1 was set
as leading axis for Axis_2.
• All synchronized drives are
processed at different run
levels.
• Set a definite leading /
following axis combination.
• Assign the leading / following
axes to the same run level
(usually the interpolator
cycle).
20007
804A The required object
interconnection is
missing
No allowances have been made
in the application program for
relevant combinations of leading
/ following axes and cam disks.
Set the required leading axes and
cam disks in the "Configuration"
section of the synchronization
object of the following axis.
30008
804B Limit switch
actuated; illegal
command
A hardware
limit switch is actuated.
Permitted are only motion
commands in direction of the
operating range.
Check the mechanical
configuration and the wiring.
Correct any programming errors
or use the software limit switches.
50009
8082 Illegal Zero value in
parameter
A command was passed
alongside with a
Zero parameter.
This value must always be
unequal to
Zero.
Check the transferred parameters,
preset values and, in particular,
the dynamic and limit values. (e.g.
max. velocity or acceleration for
positioning)
40006, 40007,
40008, 40009,
40010, 40011
8085 Illegal limit switch
parameters
Implausible position values for
the SW limit switch. One of the
values violates the range, or the
start value is higher than the end
value. The latter may occur if the
order is neglected when the
parameters are changed.
Adjust the setting of the SW limit
switch. After the first change of
the position, the position value of
the positive switch must be higher
than that of the negative switch.
40104
8090 Illegal Zero
parameter
Reserved error 40122, 40123
8091 Error in pressure
control
Reserved error 50014
8092 Error in force limit
monitoring
Reserved error 50109, 50110
* Interrupts in S7T Config, which may be associated with the indicated error.