Technical data

Technology functions
CPU 317T: Technology Functions
A5E00251798-03
6-251
ErrorID
Error message Description / to correct or avoid error
80A2 DP protocol error in layer 2 Error in data record transfer, repetition in next program
cycle possible.
PROFIBUS DP error in layer 2:
Station failure
Time-out
Protocol error
80B0 Data set not supported Error in data record transfer, command canceled.
System function not available for module type
Module does not know the data record
Data set number out of the range of 0 to 255
80B5 System function can not be
executed
Error in data record transfer, repetition in next program
cycle possible. The system function can not be executed
due to the internal processing state of the drive.
80B7 Faulty command PROFIBUS DP error, command aborted. The faulty
command could not be output.
80C3 Module at capacity limits Error in data record transfer, repetition in next program
cycle possible. Required resources currently in use by
other applications:
In the technology function "MC_WriteDriveParameter"
In the module
80C5 Access to distributed I/O failed Error in data record transfer, repetition in next program
cycle possible. Distributed I/O currently unavailable.
80C7 A command has already been
output to the drive
Error in data record transfer, repetition in next program
cycle possible. Another command has already been
output to the drive
8100 Parameter not found Parameter error, command canceled. Attempt to access a
non-existing parameter.
8101 Parameter is read-only Parameter error, command canceled. Attempt to modify a
read only parameter.
8102 Parameter limits violated Parameter error, command canceled. Attempt to write
values which are out of value limits.
8103 Subindex not found Parameter error, command canceled. Attempt to access a
non-existing subindex.
8104 Parameter not indexed Parameter error, command canceled. Attempt to access a
non-indexed parameter using the subindex.
8105 Invalid data type Parameter error, command canceled. Attempt to modify a
value to a value not supported by the data type of the
parameter.
8106
Parameter value not equal to 0
Parameter error, command canceled. Attempt to modify
with value not equal to 0.
810B No exclusive access Parameter error, command canceled. Attempt to modify
without exclusive access privileges.
8111 Access denied in current state Parameter error, command canceled. Command can not
be executed in current operating state.
8114 Illegal parameter value Parameter error, command canceled. Attempt to modify
with value which may not violate value limits, but is still not
permissible for reasons of permanent compatibility
(existing parameters with defined single values.)