Technical data

Technology functions
CPU 317T: Technology Functions
A5E00251798-03
6-247
ErrorID
Error message Description / to correct or avoid error
80B0 Data set not supported Error in data record transfer, command canceled.
System function not available for module type
Module does not know the data record
Data set number out of the range of 0 to 255
80B5 System function can not be
executed
Error in data record transfer, repetition in next program
cycle possible. The system function can not be executed
due to the internal processing state of the drive.
80B7 Faulty command Error in data record transfer, PROFIBUS DP error,
command canceled. The faulty command could not be
output.
80C3 Module at capacity limits Error in data record transfer, repetition in next program
cycle possible. Required resources currently in use by
other applications:
In the technology function "MC_ReadDriveParameter"
In the module
80C5 Access to distributed I/O failed Error in data record transfer, repetition in next program
cycle possible. Distributed I/O currently unavailable.
80C7 A command has already been
output to the drive
Error in data record transfer, repetition in next program
cycle possible. Another command has already been
output to the drive
8100 Parameter not found Parameter error, command canceled. Attempt to access a
non-existing parameter.
8103 Subindex not found Parameter error, command canceled. Attempt to access a
non-existing subindex.
8104 Parameter not indexed Parameter error, command canceled. Attempt to access a
non-indexed parameter using the subindex.
8111 Access denied in current state Parameter error, command canceled. Command can not
be executed in current operating state.
8116 Value is invalid or not supported Parameter error, command canceled. Invalid or
unsupported value for attribute, number of elements,
parameter number, or subindex, or of a combination.
8119 Axis does not exist
Parameter error, command canceled. Attempt to access to
a non-existing axis.
8120 -
8164
Reserve Reserved error codes to PROFIdrive
8165 -
81FF
Manufacturer-specific error Manufacturer-specific error codes to PROFIdrive
Errors are formed by the drive.
Note
In accordance with PROFIBUS DP V1, a DP slave can report the errors A0 to CF.
The errors A0 to CF are mapped to the ErrorID of the technology function as error
80A0 to 80CF.
When output parameter ErrorID reports an error in the range from 80A0 to 80CF
which are not listed in the list shown earlier, consult your DP slave documentation.