Technical data

Technology functions
CPU 317T: Technology Functions
A5E00251798-03
6-243
ErrorID
Error message Description / to correct or avoid error
80A2 DP protocol error in layer 2 Error in data record transfer, command canceled.
PROFIBUS DP protocol error in layer 2:
Station failure
Time-out
Protocol error
80A3 DP protocol error in user interface Error in data record transfer, command canceled.
PROFIBUS DP protocol error in user interface/user.
80B0 Data set not supported Error in data record transfer, command canceled.
System function not available for module type
Module does not know the data record
Data set number out of the range of 0 to 255
80B1 Faulty length definition Error in data record transfer, command canceled. Wrong
length definition at input parameter Data.
The data record read 240 bytes, but the ANY pointer
only points to a field with a length of 80 bytes.
The length definition in the ANY pointer is not
supported, for example, 260 bytes.
80C0 Previous write command is still busy
Error in data record transfer, the command can be
repeated immediately. The module has not yet processed
the previous write command for the same data record.
80C2 Maximum number of commands
reached
Error in data record transfer, the command can be
repeated immediately. The module is currently processing
the maximum number of commands the CPU can handle.
80C3 Module at capacity limits Error in data record transfer, the command can be
repeated immediately. Required resources are currently in
use by other applications:
In the module
80C4 Communication error Error in data record transfer, the command can be
repeated immediately. Communication error
Parity error
SW ready not set
Error in block length forwarding
Checksum error at CPU
Checksum error at module
80C5 Access to distributed I/O failed Error in data record transfer, repetition in next program
cycle possible. Distributed I/O currently unavailable.
80C6 Priority class error Error in data record transfer, repetition in next program
cycle possible.
Data set transfer canceled because of priority class
cancellation (restart or background.)
Note
In accordance with PROFIBUS DP V1, a DP slave can report the errors A0 to CF.
The errors A0 to CF are mapped to the ErrorID of the technology function as error
80A0 to 80CF.
When output parameter ErrorID reports an error in the range from 80A0 to 80CF
which are not listed in the list shown earlier, consult your DP slave documentation.