Technical data

Technology functions
CPU 317T: Technology Functions
6-194 A5E00251798-03
Parameter Data type Start value Description
Error BOOL FALSE
TRUE: Command initiation
with error.
The command is not executed;
the cause is found in the ErrorID.
FALSE: Command initiation
without error
ErrorID WORD 0
ErrorID of the Error output parameter.
Value REAL 0.0 Fetched position value
Mode = 0: Position of the following axis
Mode = 1: Position of the leading axis
MC_GetCamPoint - ErrorIDs
ErrorID
Error message Description / to correct or avoid error
0000 No error -
8001 Internal fault Faulty or inconsistent project / software.
8005 Command canceled because of
input buffer overflow
The rate at which the user program outputs commands to
the technology is too high.
8007 An internal error has occurred at the
job interface
Due to an internal problem in the S7 system, commands
can not be accepted.
Check the consistency of your project data, then
download all system data to the module again.
8043 Illegal parameter value
Concerns the input parameters Mode or DoneFlag..
8044 Task not supported by the
technology object
Send a command to a cam, for example.
8045 Illegal command with current status The cam disk is not interpolated.
804C Command output rate too high The command output rate with the same instance DB was
higher than the command interface was able to accept.
The second command is rejected in order not to violate
consistency the first.
For high command output rates, always use a separate
instance DB, or send the command again. Please note,
that although the first accepted command may be busy,
you may not be able to monitor it at the status outputs.
8050 Technology not ready During testing with breakpoints (CPU in HOLD), the
technology function has output a new command to the
technology. The command is rejected.