Technical data

Technology functions
CPU 317T: Technology Functions
A5E00251798-03
6-169
ErrorID
Error message Description / to correct or avoid error
8083 DB is not a technology DB
The DB specified at input parameter Slave or the
technology DB was not found or is not a technology DB.
8084 Invalid technology DB A technology object does not exist in the PLC for the
technology DB specified at input parameter Slave.
Download the current technology to the PLC, or
change the DB number at input parameter Slave.
The user has written invalid data to the technology DB
specified at input parameter Slave.
In "Technology Objects Management", delete and then
recreate the technology DB.
808B Parameter value of invalid REAL
format
Invalid floating-
point format of at least one input parameter
value.
Check the input parameter values or the instance DB
data. Invalid values can not be indicated in floating-point
format. They are shown on hexadecimal format
(DW16# ...).