Technical data
Technology functions
CPU 317T: Technology Functions
A5E00251798-03
6-141
ErrorID
Error message Description / to correct or avoid error
8079 No synchronous operation with
specified master
The specified master and the slave are not in
synchronism.
Synchronize the relevant axes before you call the
function.
8083 DB is not a technology DB
The DB specified at input parameter Master or Slave
does not exist or is not a technology DB.
8084 Invalid technology DB • A technology object was not found in the system for
the technology DB specified at the Master or Slave
input parameters.
Download the current technology to the PLC, or
change the DB number at the Master or Slave input
parameters.
• The user has written invalid data to the technology DB
specified at input parameter Axis.
In "Technology Objects Management", delete and
then recreate the technology DB.
808B Parameter value of invalid REAL
format
Invalid floating-
point format of at least one input parameter
value.
Check the input parameter values or the instance DB
data. Invalid values can not be indicated in floating-point
format. They are shown on hexadecimal format
(DW16# ...).